Current & Voltage Measurement in Renewable Energy

Solar PV, wind power and battery energy storage: conversion architectures, critical sensing points, grid-interface requirements and engineering trade-offs.

ADISENS Technical KnowledgeWeb article
TECHNICAL OVERVIEW

Measurement inside renewable-energy power conversion

Photovoltaic inverters, wind converters and stationary battery systems all depend on controlled energy conversion between DC and AC domains. At each conversion stage, current and voltage feedback supports regulation, protection, grid compliance and system supervision. Galvanic isolation is often structural because power stages operate at high or floating potentials relative to the low-voltage control electronics.

01 · SOLAR PHOTOVOLTAIC

From PV strings to the grid

PV field / strings
→
DC/DC + MPPT
→
DC link
→
DC/AC inverter
→
Filter / transformer
→
AC grid

String current

DC current measurement supports production monitoring and fault detection at string or MPPT level.

DC-link voltage

Continuous isolated voltage supervision protects the conversion stage against overvoltage and maintains control stability.

Inverter / AC output current

Current feedback controls the injected current and supports overcurrent and grid-fault protection.

Grid voltage

Voltage measurement supports grid-code functions and anti-islanding logic.

Utility-scale PV systems can operate at DC voltages up to around 1,500 V, while compact string inverters often favour PCB-mounted sensing because internal space is limited.

02 · WIND ENERGY

Generator → converter → DC link → grid

Generator
→
Machine-side converter
→
DC link
→
Grid-side converter
→
Step-up transformer
→
Grid

Wind turbines use current feedback on the generator side for torque and speed control, DC-link voltage supervision between converter bridges, and grid-side current measurement for active/reactive power control. Medium-voltage supervision at the point of connection supports grid-code functions such as Low Voltage Ride-Through (LVRT).

Environmental challenge

Nacelle and tower-base electronics must tolerate long-duration vibration, thermal cycling and, in offshore systems, corrosive saline environments.

03 · ENERGY STORAGE

Bidirectional sensing in BESS architectures

Battery racks
→
BMS / DC bus
→
Bidirectional PCS
→
Transformer / switchgear
→
Grid / microgrid

Battery current

Bidirectional current measurement feeds charge/discharge protection and contributes to State-of-Charge estimation by coulomb counting.

DC-bus voltage

Voltage supervision supports system protection and PCS operating-point optimisation.

AC-side current

Measured at the PCS output to control power exchange with the grid or local load.

Grid voltage

Used to supervise supply quality in grid-connected, backup and microgrid operating modes.

Offset stability and thermal drift are particularly important in battery-current measurement because small errors accumulate over time in coulomb-counting based SOC estimation.

04 · STANDARDS

Reference framework

ReferenceDomainMeasurement relevance
IEC 62109-1/-2PV inverter safetyIsolation monitoring and shutdown functions
IEC 61400-21Wind power qualityAccuracy of grid-side measurements
IEC 61869 seriesInstrument measurementAccuracy classes for metering and protection
IEC 62619Stationary lithium-ion batteriesFault detection within the battery-system measurement chain
IEC 60068 seriesEnvironmental testingMechanical and climatic qualification
Grid codesGrid connectionLVRT and voltage-monitoring requirements
05 · SIGNAL ACQUISITION

The sensor is only one part of the measurement chain

Response-time budget

Protection performance depends on sensor delay, ADC conversion and controller processing together.

EMC-aware wiring

Strong switching dv/dt and di/dt around IGBTs or MOSFETs require disciplined shielding, grounding and routing.

ADC full-scale matching

Sensor rating should use the controller's dynamic range efficiently while retaining headroom for transients.

Anti-alias filtering

Low-pass filtering must balance switching-noise attenuation with control-loop and protection response.

06 · ENGINEERING SELECTION

Different renewable segments weight the same criteria differently.

CriterionSolar PVWindBESS
DC current capabilityEssentialMainly within DC linkEssential
BidirectionalityUsually not dominantPartialEssential
Offset stabilityImportantModerateCritical for SOC
Response / bandwidthModerateHigh for grid responseHigh for protection
EnvironmentTemperature, high DC voltageVibration, corrosion, thermal cyclingTemperature, fault-current withstand

In practice, one installation often combines several sensor technologies because no single approach gives the optimum balance of isolation, accuracy, bandwidth, cost and integration at every measurement point.

ADISENS ENGINEERING

Translate the measurement requirement into the right sensing architecture.

Use the Product Selector for a first technical orientation, or share your electrical, mechanical and environmental constraints with our engineering team.