Career Knowledge Partnership
← Knowledge Center
Engineering Guide

Current & Voltage Sensor Technologies — Technical Comparison

Compare shunts, current transformers, Rogowski coils, open-loop and closed-loop Hall sensing, isolated voltage measurement and optical approaches.

ADISENS Technical KnowledgeWeb article
TECHNICAL OVERVIEW

No single sensing technology dominates every criterion.

Current and voltage measurement always involves trade-offs between galvanic isolation, bandwidth, response time, DC capability, accuracy, long-term stability, size, power consumption and cost. This article compares the principal technologies used in industrial and railway electrical systems and highlights where each approach is strongest.

Engineering principle

The correct technology is defined by the measurement function and operating environment — not by a universal hierarchy of sensor types.

01 · CURRENT MEASUREMENT

Passive current-measurement technologies

Resistive shunt

A calibrated low-value resistor is inserted in series with the conductor. The measured voltage follows Ohm's law, V = R·I. It measures AC and DC with very high bandwidth and can achieve high accuracy, but it provides no inherent galvanic isolation and dissipates power through Joule losses.

Current transformer

Magnetic coupling between a primary conductor and secondary winding provides native isolation. A conventional current transformer measures AC only and can saturate under high fault current or DC bias. IEC 61869-2 is the key reference for instrument current transformers.

Rogowski coil

An air-core winding produces a voltage proportional to di/dt. Electronic integration reconstructs the current waveform. With no ferromagnetic core it does not saturate, which is valuable for very high fault currents and wide-band transient analysis, but it does not measure DC.

02 · CURRENT MEASUREMENT

Open-loop and closed-loop Hall-effect sensing

A Hall element senses the magnetic field generated by the primary current without inserting a resistive element in the power path. Both open-loop and closed-loop architectures can measure AC and DC while maintaining galvanic isolation.

OPEN LOOP

Direct field measurement

The Hall signal is amplified directly. The architecture is compact and cost-effective, but accuracy is more sensitive to Hall offset and temperature drift.

CLOSED LOOP

Flux compensation

A secondary compensation winding continuously drives the net core flux toward zero. The resulting secondary current is proportional to the primary current, improving linearity, accuracy and thermal stability at the cost of greater complexity and power consumption.

03 · COMPARISON

Current sensing at a glance

TechnologyDC capabilityGalvanic isolationTypical bandwidthTypical accuracy
Resistive shuntYesNoDC to 1 MHz+0.1–0.5%
Current transformerNoNative~15 Hz–100 kHz0.2–1%
Rogowski coilNoNative~2 Hz–30 MHz~0.5%
Hall — open loopYesYesDC to ~100 kHz1–2%
Hall — closed loopYesYesDC to ~300 kHz<0.5%

Bandwidth and accuracy values are technology-level indications from the source article, not product-level specifications.

04 · VOLTAGE MEASUREMENT

Approaches to isolated voltage measurement

Resistive divider

A resistor network scales the measured voltage to an electronics-compatible level. It is simple and wide-band, but does not inherently provide galvanic isolation and is sensitive to high-voltage resistor drift and leakage in polluted or humid environments.

Capacitive divider

A capacitive ratio performs the voltage scaling without continuous resistive dissipation. Its response depends strongly on frequency and parasitic capacitance, which limits transient accuracy.

Isolated Hall-based voltage sensor

A precision high-voltage resistor converts the voltage into a small current, which is then measured by an isolated Hall current transducer. This combines galvanic isolation with good DC capability and stability.

Optical / Pockels sensing

An electro-optical crystal changes light polarisation according to the applied electric field. The optical link is intrinsically dielectric and highly immune to electromagnetic interference, but the architecture is more complex and costly.

TechnologyIsolationFrequency dependenceTypical use
Resistive dividerNo inherent galvanic isolationLowLV/MV, cost-controlled measurement
Capacitive dividerNo inherent galvanic isolationMarkedHV capacitive voltage measurement
Isolated HallGalvanicLowMV/HV where isolation and DC capability matter
Optical / PockelsDielectricVery lowHVDC, smart grids, extreme EMC environments
05 · ENGINEERING SELECTION

Choose by function, not by habit.

DC measurement

Shunts and Hall-effect technologies can reproduce a DC component; conventional current transformers and Rogowski coils cannot.

Fast transient capture

Rogowski coils and shunts provide very wide bandwidth for dynamic protection and harmonic analysis.

Galvanic isolation

Magnetic or optical coupling is structurally valuable when power circuits must be safely separated from low-voltage control electronics.

Accuracy & stability

Closed-loop compensation is attractive where low drift and high linearity are important for protection selectivity or precision measurement.

ApplicationMeasured quantityTechnology directionMain reason
Protection / selectivityCurrentRogowski or closed-loop HallFast response, fault-current behaviour
Energy meteringCurrentCT or precision closed-loop HallAccuracy and stability
Power quality / harmonicsCurrentRogowski or shuntWide bandwidth
MV/HV voltage supervisionVoltageIsolated Hall or dedicated dividerIsolation and control accuracy
HVDC / smart gridVoltageOpticalEMC immunity and dielectric isolation
REFERENCE

Glossary

Galvanic isolation. Electrical separation between two circuits with no direct conductive path.

Bandwidth. Frequency range over which the measurement chain reproduces the signal within its specified performance.

Magnetic saturation. A core condition in which further primary-current increase can no longer produce a proportional magnetic response.

IEC 61869. International series covering instrument transformers and measurement transformers, including accuracy classes.

Selectivity. Protection strategy in which only the protective device closest to a fault opens, leaving the rest of the installation energised.

ADISENS ENGINEERING

Translate the measurement requirement into the right sensing architecture.

Use the Product Selector for a first technical orientation, or share your electrical, mechanical and environmental constraints with our engineering team.